100A2FHT1RA0310

Overall Cable Diameter

76mm -91mm

GTIN/EAN Code

5052625370391

ETIM Classification

EC000441

Downloads

Description

The A2FHT range of cable glands are for use in heavy duty applications in Explosive Atmospheres. Designed for high temperature applications.


Features

  • -60˚C to +180˚C high temperature ThermEx seals
  • Displacement type flameproof seal
  • Deluge protected
  • Internationally marked, UKEX, IECEx and ATEX

Additional Information

Technical Specification
Maximum Across Flats 'AF' 123.2
Maximum Across Flats 'AF' (Imperial) 4.85
Maximum Across Corners 'AC' (Imperial) 5.34
Compliance Standard NPT Tapered Thread to ANSI B1.20.1:2006 / ASME B1.20.1:2013 gauging to clause 8.1 for external thread & IEC 60981:2004-05
Refresh Comments Imperial data refresh
Minimum Overall Cable Diameter 'OS' 76
Minimum Overall Cable Diameter 'OS' (Imperial) 2.99
Maximum Overall Cable Diameter 'OS' 91
Maximum Overall Cable Diameter 'OS' (Imperial) 3.58
Minimum Thread Length 'TL' 44
Minimum Thread Length 'TL' (Imperial) 1.73
Certification
ATEX Certificate Number CML 18ATEX1308X
ATEX Code of Protection ^ II 2G 3G 1D Ex db IIC Gb, Ex eb IIC Gb, Ex nR IIC Gc, Ex ta IIIC Da
ATEX Compliance Standards EN 60079-0, -1, -7, -15, -31
IECEx Certificate Number IECEx CML 18.0173X
IECEx Code of Protection Ex db IIC Gb, Ex eb IIC Gb, Ex nR IIC Gc, Ex ta IIIC Da
IECEx Compliance Standards IEC 60079-0, -1, -7, -15, -31
IECEx Logo Filename iecexlogo.jpg
IECEx Logo https://cdn.pimber.ly/public/asset/raw/62c2cfa03a6b3a001b063277/990ba9ce/6447a914b902aa64e3000252/iecexlogo.jpg
UKEX Certificate Number CML 21UKEX1249X, CML 21UKEX4250X
EAC Certificate Number EAЭC RU C-GB.AꙢ07.B.02519/20
EAC Code of Protection { 1Ex db IIC Gb X, { 1Ex e IIC Gb X, { 2Ex nR IIC Gc X, { Ex ta IIIC Da X
EAC Logo Filename eaclogo.jpg
EAC Logo https://cdn.pimber.ly/public/asset/raw/62c2cfa03a6b3a001b063277/0802384c/64425917f6310520f0000001/eaclogo.jpg
PESO Certificate Number P533772/2, P548696/9
ECAS Certificate Number 23-03-64846/E23-02-065475_NB0007
ECAS Logo Filename ecaslogo.jpg
SANS Certificate Number S-XPL21804 21.0003X
ETIM
Thread type NPT
Nominal thread size inch/gas pipe thread 4 inch
Thread length 44
Wrench width 123.2
Hexagon angular dimension 135.5
Suitable for cable diameter 76
Suitable for cable diameter max 91
Material Metal
Material quality Brass
Surface protection Untreated
Halogen free Yes
Glass-fibre reinforced No
Degree of protection (IP) IP68
Shock resistant Yes
Colour Brass
Bend radius protection/trumpet flare No
With locknut No
Snapping in opening No
Model Straight
Multi seal area No
Flat cable coupling No
With strain relief No
Type of sealing Sealing ring
Explosion-tested version Yes
Operating temperature max 180
For Ex-zone gas 1, 2
For Ex-Zone dust 20, 21, 22
For armoured cable No
EMC-version No
Screened No

Certificates

2D/3D Illustrations