Description
The SS2KHT range of cable glands are for use in heavy duty applications in Explosive Atmospheres. Designed for high temperature applications.
Features
- -20˚C to 200˚C high temperature ThermEx seals
- Provides double seal on outer sheath or single on outer & inner
- Direct & remote installation
- Superior levels of cable retention
- Displacement type flameproof seals
- Deluge protected
- Internationally marked UKEX, IECEx & ATEX
|
Technical Specification
|
| Maximum Across Flats 'AF' |
123 |
| Maximum Across Flats 'AF' (Imperial) |
4.85 |
| Maximum Across Corners 'AC' (Imperial) |
5.33 |
| Compliance Standard |
Metric Parallel Thread to ISO 965-1:2013, ISO 965-3:1998 (& Corrigendum 1 - 2009), medium fit (6g) for external thread |
| Refresh Comments |
Imperial data refresh |
| Minimum Cable Bedding Diameter 'IB' |
76 |
| Minimum Cable Bedding Diameter 'IB' (Imperial) |
2.99 |
| Maximum Cable Bedding Diameter 'IB' |
91 |
| Maximum Cable Bedding Diameter 'IB' (Imperial) |
3.58 |
| Minimum Overall Cable Diameter 'OS' |
76 |
| Minimum Overall Cable Diameter 'OS' (Imperial) |
2.99 |
| Maximum Overall Cable Diameter 'OS' |
90.9 |
| Maximum Overall Cable Diameter 'OS' (Imperial) |
3.58 |
| Minimum Thread Length 'TL' |
24 |
| Minimum Thread Length 'TL' (Imperial) |
0.94 |
|
|
Certification
|
| ATEX Certificate Number |
CML 18ATEX1322X |
| ATEX Code of Protection |
^ I M2 Ex db I Mb, Ex eb I Mb; ^ II 2G 3G 1D Ex db IIC Gb, Ex eb IIC Gb, Ex nR IIC Gc, Ex ta IIIC Da |
| ATEX Compliance Standards |
EN 60079-0, -1, -7, -15, -31 |
| IECEx Certificate Number |
IECEx CML 18.0178X |
| IECEx Code of Protection |
Ex db I Mb, Ex eb I Mb, Ex db IIC Gb, Ex eb IIC Gb, Ex nR IIC Gc, Ex ta IIIC Da |
| IECEx Compliance Standards |
IEC 60079-0, -1, -7, -15, -31 |
| IECEx Logo Filename |
iecexlogo.jpg |
| IECEx Logo |
https://cdn.pimber.ly/public/asset/raw/62c2cfa03a6b3a001b063277/990ba9ce/6447a914b902aa64e3000252/iecexlogo.jpg |
| UKEX Certificate Number |
CML 21UKEX1256X, CML 21UKEX4257X |
| EAC Certificate Number |
EAЭC RU C-GB.AꙢ07.B.04596/22 |
| EAC Code of Protection |
{ 1Ex db IIC Gb X, { 1Ex e IIC Gb X, { 2Ex nR IIC Gc X, { Ex ta IIIC Da X |
| EAC Logo Filename |
eaclogo.jpg |
| EAC Logo |
https://cdn.pimber.ly/public/asset/raw/62c2cfa03a6b3a001b063277/0802384c/64425917f6310520f0000001/eaclogo.jpg |
| KCs Certificate Number |
19-AV4BO-0258X |
| KCs Logo Filename |
kcslogo.jpg |
| KCs Logo |
https://cdn.pimber.ly/public/asset/raw/62c2cfa03a6b3a001b063277/0802384c/64425917f6310520f0000007/kcslogo.jpg |
| CCC Certificate Number |
2020322313002869 |
| CCC Logo Filename |
ccclogo.jpg |
| CCC Logo |
https://cdn.pimber.ly/public/asset/raw/62c2cfa03a6b3a001b063277/cf29f9f6/644a38e4f631055a56000001/ccclogo.jpg |
| RETIE Certificate Number |
3866 |
| PESO Certificate Number |
P533772/3, P548696/10 |
| ECAS Certificate Number |
23-03-64828/E23-02-065423/NB0007 |
| ECAS Logo Filename |
ecaslogo.jpg |
| SANS Certificate Number |
MS-XPL21804 21.0007X |
|
|
ETIM
|
| Thread type |
Metric |
| Nominal thread size metric/PG |
100 |
| Pitch thread |
2 |
| Thread length |
24 |
| Wrench width |
123 |
| Hexagon angular dimension |
135.3 |
| Suitable for cable diameter |
76 |
| Suitable for cable diameter max |
90.9 |
| Material |
Metal |
| Material quality |
Brass |
| Surface protection |
Nickel-plated |
| Halogen free |
Yes |
| Glass-fibre reinforced |
No |
| Degree of protection (IP) |
IP68 |
| Shock resistant |
Yes |
| Colour |
Nickel |
| Bend radius protection/trumpet flare |
No |
| With locknut |
No |
| Snapping in opening |
No |
| Model |
Straight |
| Multi seal area |
No |
| Flat cable coupling |
No |
| With strain relief |
No |
| Type of sealing |
Sealing ring |
| Explosion-tested version |
Yes |
| Operating temperature max |
200 |
| For Ex-zone gas |
1, 2 |
| For Ex-Zone dust |
20, 21, 22 |
| For armoured cable |
No |
| EMC-version |
No |
| Screened |
No |
|