The Triton CDS PB range of cable glands are for use in heavy duty applications in Explosive Atmospheres. Designed with a unique compensating displacement seal (CDS) to reduce the effects of coldflow.
Features
Effectively earths / grounds lead sheathed cables
Fully sequential, three step installation procedure
Direct and remote installation
Unique compensating displacement seal system (CDS)
Metal-to-metal installation every time regardless of lead sheath diameter
Designed to reduce the effects of coldflow, see CMP Technical Document TS002
Integral protected deluge seal
Controlled outer load retention seal
Unique OSTG prevents overtightening
-60˚C to +130˚C
Globally marked IECEx, ATEX and UKEX
Superior EMC performance
Additional Information
Technical Specification
Maximum Across Flats 'AF'
127
Maximum Across Flats 'AF' (Imperial)
5
Maximum Across Corners 'AC' (Imperial)
5.5
Compliance Standard
NPT Tapered Thread to ANSI B1.20.1:2006 / ASME B1.20.1:2013 gauging to clause 8.1 for external thread & IEC 60981:2004-05
Refresh Comments
Imperial data refresh
Minimum Armour Thickness W (Stepped) Cone 'W1' (Imperial)
0.124
Minimum Armour Thickness W (Stepped) Cone 'W1'
3.15
Maximum Armour Thickness W (Stepped) Cone 'W1' (Imperial)
0.157
Maximum Armour Thickness W (Stepped) Cone 'W1'
4
Minimum Armour Thickness X (Grooved) Cone 'X1' (Imperial)
0.03
Minimum Armour Thickness X (Grooved) Cone 'X1'
0.8
Maximum Armour Thickness X (Grooved) Cone 'X1' (Imperial)
0.06
Minimum Lead Sheath Diameter
76
Minimum Lead Sheath Diameter (Imperial)
2.99
Maximum Lead Sheath Diameter
88.1
Maximum Lead Sheath Diameter (Imperial)
3.47
Minimum Overall Cable Diameter 'OS'
86.1
Minimum Overall Cable Diameter 'OS' (Imperial)
3.39
Maximum Overall Cable Diameter 'OS'
101.4
Maximum Overall Cable Diameter 'OS' (Imperial)
3.99
Minimum Thread Length 'TL'
42.8
Minimum Thread Length 'TL' (Imperial)
1.69
Certification
ATEX Certificate Number
CML 18ATEX1326X
ATEX Code of Protection
^ I M2 Ex db I Mb, Ex eb I Mb; ^ II 2G 3G 1D Ex db IIC Gb, Ex eb IIC Gb, Ex nR IIC Gc, Ex ta IIIC Da
ATEX Compliance Standards
EN 60079-0, -1, -7, -15, -31
IECEx Certificate Number
IECEx CML 18.0183X
IECEx Code of Protection
Ex db I Mb, Ex eb I Mb, Ex db IIC Gb, Ex eb IIC Gb, Ex nR IIC Gc, Ex ta IIIC Da