1BC-LUL Cable Cleat

ETIM Classification

EC004588

Polymeric (LUL approved) single formation, 1 bolt cable cleat

Description

The CMP Sabre (LUL) is a single non-metallic (polymeric) cable cleat, designed and tested in accordance with IEC 61914. Manufactured from Injection Moulded, Low Smoke & Fume, Zero Halogen (LSF0H) and Phosphorus Free, LUL Approved Polymer. Due to its unique twin arc internal profile, this product exhibits excellent cable retention, limiting both axial and lateral cable movement. The single fixing design provides quick and easy installation in any orientation the cable route may take. There is one M10 clearance hole for versatile fixing of the cable cleat.


Features

  • Third party certified to IEC 61914, Lloyds, Bureau Veritas, ABS , GOST-R
  • Injection Moulded, Low Smoke & Fume, Zero Halogen (LSF0H) and Phosphorus Free, LUL Approved Polymer
  • Single formation
  • Short circuit rating of 68kA
  • Operating temperature -40°C to +60°C
  • Single (M10) clearance hole for fixing.

Additional Information

Certification
Technical Specification
Axial Load Test Range, IEC 61914 clause 9.4 Information on request
Cable Formation Single
Classification IEC61914 clause 6.1 6.1.2 Non-Metallic
Cleat Material LUL Approved Polymer. Low smoke and fume (LSF), Zero Halogen (LS0H) and Phosphorus Free
Conductor centres - A (mm) 105
Conductor centres - B (mm) 18.8
Conductor centres - C (mm) 18.8
Fixed cleat centres A (mm) 600
Fixed cleat centres B (mm) 600
Fixed cleat centres C (mm) 600
Impact Resistance, IEC 61914 clause 6.3 Very heavy
kA RMS - A 32.3
kA RMS - B 51.3
kA RMS - C 51.3
Lateral Load Test Range, IEC 61914 clause 9.3 Information on request
Needle Flame Test, IEC61914 clause 10, 10.1, IEC 60695-11-5 Pass 120 Second
No of tests - A 1
No of tests - B 1
No of tests - C 2
Peak short circuit current A (kA) 68
Peak short circuit current B (kA) 113
Peak short circuit current C (kA) 113
SC Duration A (Seconds) 0.1
SC Duration B (Seconds) 0.1
SC Duration C (Seconds) 0.1
Temperature For Permanent Application, IEC 61914 clause 6.2 -40°C to +60°C