The C2KHT range of cable glands are for use in heavy duty applications in Explosive Atmospheres. Designed for high temperature applications with a single seal on the cable outer sheath and an integral protected deluge seal.
Features
-20˚C to 200˚C high temperature ThermEx seals
Metal-to-metal armour clamping
Direct & remote installation
Integral protected deluge seal
Displacement type flameproof seal
Controlled outer ‘load retention’ seal
Internationally marked, UKEX, IECEx & ATEX
Superior EMC performance
Additional Information
Technical Specification
Maximum Across Flats 'AF'
24
Maximum Across Flats 'AF' (Imperial)
0.95
Maximum Across Corners 'AC' (Imperial)
1.04
Compliance Standard
NPT Tapered Thread to ANSI B1.20.1:2006 / ASME B1.20.1:2013 gauging to clause 8.1 for external thread & IEC 60981:2004-05
Refresh Comments
Imperial data refresh
Minimum Armour Thickness W (Stepped) Cone 'W1' (Imperial)
0.031
Minimum Armour Thickness W (Stepped) Cone 'W1'
0.8
Maximum Armour Thickness W (Stepped) Cone 'W1' (Imperial)
0.049
Maximum Armour Thickness W (Stepped) Cone 'W1'
1.25
Minimum Armour Thickness X (Grooved) Cone 'X1' (Imperial)
0.01
Minimum Armour Thickness X (Grooved) Cone 'X1'
0.3
Maximum Armour Thickness X (Grooved) Cone 'X1' (Imperial)
0.04
Minimum Cable Bedding Diameter 'IB' (Imperial)
0
Maximum Cable Bedding Diameter 'IB'
11.7
Maximum Cable Bedding Diameter 'IB' (Imperial)
0.46
Minimum Overall Cable Diameter 'OS'
9.5
Minimum Overall Cable Diameter 'OS' (Imperial)
0.37
Maximum Overall Cable Diameter 'OS'
15.9
Maximum Overall Cable Diameter 'OS' (Imperial)
0.63
Minimum Thread Length 'TL'
19.9
Minimum Thread Length 'TL' (Imperial)
0.78
Certification
ATEX Certificate Number
CML 18ATEX1323X
ATEX Code of Protection
^ II 2G 3G 1D Ex db IIC Gb, Ex eb IIC Gb, Ex nR IIC Gc, Ex ta IIIC Da