32TFU504

Overall Cable Diameter

21.5mm -33.9mm

Downloads

Description

The TFU range of cable glands are for use in heavy duty applications in Explosive Atmospheres. For all types of Armoured or Braided / Screened cables. Designed with a unique adaptive cone and no loose components.


Features

  • Flameproof inner diaphragm seal – safe, reliable & robust; no installation or inspection ambiguity
  • Excellent cold flow performance with third party verified test report on cable types used globally
  • Unique patented captive ‘Adaptive’ armour cone for all types of armour or braid, with captive ‘AnyWay’ clamping ring
  • Metal-to-metal armour clamping; no installation or inspection ambiguity
  • Fewer installation steps for faster process. Unique ‘Quick’ thread for faster armour clamping
  • Outer seal with wider cable acceptance, meaning fewer stocking sizes
  • IP66, 67, 68, 69 & 69K as standard with fully enclosed/protected deluge seal for third party compliance to DTS 01
  • Compact design; ideal for applications with limited installation space
  • Fewer tools required for installation and maintenance

Additional Information

Technical Specification
Maximum Across Flats 'AF' 46
Maximum Across Flats 'AF' (Imperial) 1.81
Maximum Across Corners 'AC' 50.6
Maximum Across Corners 'AC' (Imperial) 1.99
Compliance Standard Metric Parallel Thread to ISO 965-1:2013, ISO 965-3:1998 (& Corrigendum 1 - 2009), medium fit (6g) for external thread
Minimum Armour Thickness W (Stepped) Cone 'W1' (Imperial) 0.06
Minimum Armour Thickness W (Stepped) Cone 'W1' 1.6
Maximum Armour Thickness W (Stepped) Cone 'W1' (Imperial) 0.08
Maximum Armour Thickness W (Stepped) Cone 'W1' 2
Minimum Armour Thickness X (Grooved) Cone 'X1' (Imperial) 0.01
Minimum Armour Thickness X (Grooved) Cone 'X1' 0.2
Maximum Armour Thickness X (Grooved) Cone 'X1' (Imperial) 0.02
Minimum Cable Bedding Diameter 'IB' 17
Minimum Cable Bedding Diameter 'IB' (Imperial) 0.67
Maximum Cable Bedding Diameter 'IB' 26.5
Maximum Cable Bedding Diameter 'IB' (Imperial) 1.04
Minimum Overall Cable Diameter 'OS' 21.5
Minimum Overall Cable Diameter 'OS' (Imperial) 0.85
Maximum Overall Cable Diameter 'OS' 33.9
Maximum Overall Cable Diameter 'OS' (Imperial) 1.33
Minimum Thread Length 'TL' 15
Minimum Thread Length 'TL' (Imperial) 0.59
Certification
ETIM

Certificates