Description
The BWL range of cable glands are for use in heavy duty applications in Industrial Areas (Safe Areas). For all types of Steel and Aluminium Wire Armoured cables. Designed generally for indoor areas as no sealing protection is provided for the cable.
Features
High quality durable materials Simple, effective two part arrangement Metal-to-metal armour clamping Direct & remote installation Permanently crimped, low impedance earth termination Secure against self-loosening Robust, heavy duty design Longer body protects armour wires from impact -60˚C to +200˚C Superior EMC performance
Technical Specification
Maximum Across Flats 'AF'
80
Maximum Across Flats 'AF' (Imperial)
3.15
Maximum Across Corners 'AC'
88
Maximum Across Corners 'AC' (Imperial)
3.46
Compliance Standard
Metric Parallel Thread to ISO 965-1:2013, ISO 965-3:1998 (& Corrigendum 1 - 2009), medium fit (6g) for external thread
Minimum Armour Thickness W (Stepped) Cone 'W1' (Imperial)
0.08
Minimum Armour Thickness W (Stepped) Cone 'W1'
2
Maximum Armour Thickness W (Stepped) Cone 'W1' (Imperial)
0.1
Maximum Armour Thickness W (Stepped) Cone 'W1'
2.5
Minimum Cable Bedding Diameter 'IB'
41.5
Minimum Cable Bedding Diameter 'IB' (Imperial)
1.63
Maximum Cable Bedding Diameter 'IB'
55
Maximum Cable Bedding Diameter 'IB' (Imperial)
2.17
Minimum Overall Cable Diameter 'OS'
52
Minimum Overall Cable Diameter 'OS' (Imperial)
2.05
Maximum Overall Cable Diameter 'OS'
66
Maximum Overall Cable Diameter 'OS' (Imperial)
2.6
Minimum Thread Length 'TL'
15
Minimum Thread Length 'TL' (Imperial)
0.59