The PX2KPB range of compound barrier cable glands are for use in heavy duty applications in Explosive Atmospheres. Designed to prevent gas, vapour or fluid from migrating through a cable, or else prevent flame transmission from a Flameproof type ‘d’ enclosure, as determined by IEC 60079-14
Features
Effectively earths / grounds lead sheathed cables
Metal-to-metal armour clamping
Direct and remote installation
Compound barrier type flameproof seal
Controlled outer load retention seal
Unique OSTG prevents overtightening
Integral protected deluge seal
-60˚C to +85˚C
Internationally marked, UKEX, IECEx and ATEX
Superior EMC performance
Compound barrier seals around internal cable cores after removing any inner cable sheath/bedding; completely eliminating any risk of coldflow
Additional Information
Technical Specification
Maximum Across Flats 'AF'
90
Maximum Across Flats 'AF' (Imperial)
3.55
Maximum Across Corners 'AC' (Imperial)
3.9
Compliance Standard
Metric Parallel Thread to ISO 965-1:2013, ISO 965-3:1998 (& Corrigendum 1 - 2009), medium fit (6g) for external thread
Refresh Comments
Imperial data refresh
Minimum Armour Thickness W (Stepped) Cone 'W1' (Imperial)
0.079
Minimum Armour Thickness W (Stepped) Cone 'W1'
2
Maximum Armour Thickness W (Stepped) Cone 'W1' (Imperial)
0.098
Maximum Armour Thickness W (Stepped) Cone 'W1'
2.5
Minimum Armour Thickness X (Grooved) Cone 'X1' (Imperial)
0.02
Minimum Armour Thickness X (Grooved) Cone 'X1'
0.6
Maximum Armour Thickness X (Grooved) Cone 'X1' (Imperial)
0.06
Minimum Lead Sheath Diameter
52.8
Minimum Lead Sheath Diameter (Imperial)
2.08
Maximum Lead Sheath Diameter
60.2
Maximum Lead Sheath Diameter (Imperial)
2.37
Minimum Overall Cable Diameter 'OS'
59
Minimum Overall Cable Diameter 'OS' (Imperial)
2.32
Maximum Overall Cable Diameter 'OS'
72
Maximum Overall Cable Diameter 'OS' (Imperial)
2.83
Minimum Thread Length 'TL'
15
Minimum Thread Length 'TL' (Imperial)
0.59
Certification
ATEX Certificate Number
CML 18ATEX1325X
ATEX Code of Protection
^ I M2 Ex db I Mb, Ex eb I Mb; ^ II 2G 3G 1D Ex db IIC Gb, Ex eb IIC Gb, Ex nR IIC Gc, Ex ta IIIC Da
ATEX Compliance Standards
EN 60079-0, -1, -7, -15, -31
IECEx Certificate Number
IECEx CML 18.0182X
IECEx Code of Protection
Ex db I Mb, Ex eb I Mb, Ex db IIC Gb, Ex eb IIC Gb, Ex nR IIC Gc, Ex ta IIIC Da