75SS2K1RA138

Overall Cable Diameter

61.1mm -67.9mm

GTIN/EAN Code

5052625439302

ETIM Classification

EC000441

Downloads

Description

The SS2K range of cable glands are for use in heavy duty applications in Explosive Atmospheres. Designed with a seal on both the inner and the outer sheath, or a double seal on the cable outer sheath.


Features

  • Provides double seal on outer sheath or single on outer and inner
  • Direct and remote installation
  • Superior levels of cable retention
  • Displacement type flameproof seal
  • Deluge protected
  • -60˚C to +130˚C (standard)
  • Ex e only version available
  • Globally marked, UKEX, IECEx, ATEX and CSA

Additional Information

Technical Specification
Maximum Across Flats 'AF' 100
Maximum Across Flats 'AF' (Imperial) 3.94
Maximum Across Corners 'AC' (Imperial) 4.33
Compliance Standard NPT Tapered Thread to ANSI B1.20.1:2006 / ASME B1.20.1:2013 gauging to clause 8.1 for external thread & IEC 60981:2004-05
Refresh Comments Imperial data refresh
Minimum Cable Bedding Diameter 'IB' 61.1
Minimum Cable Bedding Diameter 'IB' (Imperial) 2.41
Maximum Cable Bedding Diameter 'IB' 67.9
Maximum Cable Bedding Diameter 'IB' (Imperial) 2.67
Minimum Overall Cable Diameter 'OS' 61.1
Minimum Overall Cable Diameter 'OS' (Imperial) 2.41
Maximum Overall Cable Diameter 'OS' 67.9
Maximum Overall Cable Diameter 'OS' (Imperial) 2.67
Minimum Thread Length 'TL' 41.5
Minimum Thread Length 'TL' (Imperial) 1.63
Certification
ATEX Certificate Number CML 18ATEX1322X
ATEX Code of Protection ^ II 2G 3G 1D Ex db IIC Gb, Ex eb IIC Gb, Ex nR IIC Gc, Ex ta IIIC Da
ATEX Compliance Standards EN 60079-0, -1, -7, -15, -31
IECEx Certificate Number IECEx CML 18.0178X
IECEx Code of Protection Ex db IIC Gb, Ex eb IIC Gb, Ex nR IIC Gc, Ex ta IIIC Da
IECEx Compliance Standards IEC 60079-0, -1, -7, -15, -31
IECEx Logo Filename iecexlogo.jpg
IECEx Logo https://cdn.pimber.ly/public/asset/raw/62c2cfa03a6b3a001b063277/990ba9ce/6447a914b902aa64e3000252/iecexlogo.jpg
UKEX Certificate Number CML 21UKEX1256X, CML 21UKEX4257X
CSA Certificate Number CSA Certificate
CSA Code of Protection Ex e II, Ex nR II, Enclosure Type 4X
CSA Logo Filename csalogo.jpg
CSA Logo https://cdn.pimber.ly/public/asset/raw/62c2cfa03a6b3a001b063277/0802384c/64425917f6310520f0000012/csalogo.jpg
EAC Certificate Number EAЭC RU C-GB.AꙢ07.B.04596/22
EAC Code of Protection { 1Ex db IIC Gb X, { 1Ex e IIC Gb X, { 2Ex nR IIC Gc X, { Ex ta IIIC Da X
EAC Logo Filename eaclogo.jpg
EAC Logo https://cdn.pimber.ly/public/asset/raw/62c2cfa03a6b3a001b063277/0802384c/64425917f6310520f0000001/eaclogo.jpg
KCs Certificate Number 19-AV4BO-0258X
KCs Logo Filename kcslogo.jpg
KCs Logo https://cdn.pimber.ly/public/asset/raw/62c2cfa03a6b3a001b063277/0802384c/64425917f6310520f0000007/kcslogo.jpg
CCC Certificate Number 2020322313002869
CCC Logo Filename ccclogo.jpg
CCC Logo https://cdn.pimber.ly/public/asset/raw/62c2cfa03a6b3a001b063277/cf29f9f6/644a38e4f631055a56000001/ccclogo.jpg
RETIE Certificate Number 3866
PESO Certificate Number P533772/3, P548696/10
PESO Logo https://cdn.pimber.ly/public/asset/raw/62c2cfa03a6b3a001b063277/0802384c/64425917f6310520f000000a/pesologo.jpg
ECAS Certificate Number 23-03-64828/E23-02-065423/NB0007
ECAS Logo Filename ecaslogo.jpg
SANS Certificate Number MS-XPL21804 21.0007X
ETIM
Thread type NPT
Nominal thread size inch/gas pipe thread 3 inch
Thread length 41.5
Wrench width 100
Hexagon angular dimension 110
Suitable for cable diameter 61.1
Suitable for cable diameter max 67.9
Material Metal
Material quality Aluminium
Surface protection Untreated
Halogen free Yes
Glass-fibre reinforced No
Degree of protection (IP) IP68
Shock resistant Yes
Colour Silver
Bend radius protection/trumpet flare No
With locknut No
Snapping in opening No
Model Straight
Multi seal area No
Flat cable coupling No
With strain relief No
Type of sealing Sealing ring
Explosion-tested version Yes
Operating temperature max 130
For Ex-zone gas 1, 2
For Ex-Zone dust 20, 21, 22
For armoured cable No
EMC-version No
Screened No

Certificates

2D/3D Illustrations