HDSS Cable Cleat

ETIM Classification

EC004588

Side opening heavy duty stainless steel, hinged trefoil cable cleat

Description

The CMP Sovereign is a trefoil composite cable cleat, designed and tested in accordance with IEC 61914. Manufactured from 316L Stainless Steel with Low Smoke & Fume, Zero Halogen (LSF0H), Phosphorus free polymeric liners to protect the cable sheath. The cable cleat has been designed and tested for high short circuit fault withstand on cables held in trefoil formation, to ensure the securing and retention of cables without cable damage. The fully opening hinge allows the cable cleat to be opened wide for easy cable installation, and the single closing fixture with captive bolt ensures a quick installation. The two M10 and one M12 fixing clearance holes in the base allows versatility of fixing the cleat to the mounting structure.


Features

  • Third party certified to IEC 61914, DNV, Lloyds, Bureau Veritas, RMRS, UL, GOST-R, LUL
  • 316L Stainless Steel
  • Trefoil formation
  • Short circuit rating of 190kA
  • Operating temperature -60°C to +60°C
  • Combined single (M12) or two bolt (M10) base fixing

Additional Information

Certification
Technical Specification
Axial Load Test Range, IEC 61914 clause 9.4 700N
Cable Formation Trefoil
Classification IEC61914 clause 6.1 6.1.3 Composite
Cleat Material 316L Stainless Steel with standard liners. Liners are classified as Low Smoke & Fume (LSF), Zero Halogen (LS0H) and Phosphorus Free.
Conductor centres - A (mm) 36
Conductor centres - B (mm) 36
Conductor centres - C (mm) 36
Conductor centres - D (mm) 36
Fixed cleat centres A (mm) 300
Fixed cleat centres B (mm) 300
Fixed cleat centres C (mm) 600
Fixed cleat centres D (mm) 600
Impact Resistance, IEC 61914 clause 6.3 Very heavy
kA RMS - A 87.7
kA RMS - B 46.1
kA RMS - C 68.2
kA RMS - D 38.1
Lateral Load Test Range, IEC 61914 clause 9.3 4kN - 9kN
Needle Flame Test, IEC61914 clause 10, 10.1, IEC 60695-11-5 Pass 120 Second
No of tests - A 1
No of tests - B 1
No of tests - C 2
No of tests - D 2
Peak short circuit current A (kA) 190
Peak short circuit current B (kA) 96
Peak short circuit current C (kA) 150
Peak short circuit current D (kA) 80
SC Duration A (Seconds) 0.1
SC Duration B (Seconds) 1
SC Duration C (Seconds) 0.1
SC Duration D (Seconds) 1
Temperature For Permanent Application, IEC 61914 clause 6.2 -60°C to +60°C

Downloads

Certificates

Product Selector

1
Part Number Cable Ø range take (mm) Width (W) Height (H) Depth (D) Hole Pitch (P) Base Fixing Ø (D1) Base Fixing Ø (D2) Weight (g)
HDSS017021 17-21 99 88 54 25 2 x M10 1 x M12 406
HDSS019023 19-23 100 87 54 25 2 x M10 1 x M12 417
HDSS023028 23-28 104 88 54 25 2 x M10 1 x M12 450
HDSS027032 27-32 106 97 54 25 2 x M10 1 x M12 465
HDSS030035 30-35 108 103 54 25 2 x M10 1 x M12 473
HDSS033038 33-38 110 107 54 25 2 x M10 1 x M12 485
HDSS036042 36-42 132 108 54 50 2 x M10 1 x M12 570
HDSS040046 40-46 134 113 54 50 2 x M10 1 x M12 581
HDSS044050 44-50 136 121 54 50 2 x M10 1 x M12 594
HDSS048055 48-55 138 127 54 50 2 x M10 1 x M12 616
HDSS051058 51-58 140 130 54 50 2 x M10 1 x M12 627
HDSS055062 55-62 157 138 54 75 2 x M10 1 x M12 704
HDSS059066 59-66 157 145 54 75 2 x M10 1 x M12 718
HDSS063070 63-70 160 152 54 75 2 x M10 1 x M12 733
HDSS067074 67-74 163 160 54 75 2 x M10 1 x M12 748
HDSS071078 71-78 168 167 54 75 2 x M10 1 x M12 764
HDSS074082 74-82 190 175 54 75 2 x M10 1 x M12 863
HDSS077085 77-85 192 180 54 75 2 x M10 1 x M12 873
HDSS082088 82-88 193 186 54 75 2 x M10 1 x M12 883
HDSS088096 88-96 202 201 54 75 2 x M10 1 x M12 914
HDSS096103 96-103 214 215 54 75 2 x M10 1 x M12 942
HDSS103111 103-111 237 229 54 75 2 x M10 1 x M12 1055
HDSS111119 111-119 248 244 54 75 2 x M10 1 x M12 1086
HDSS119128 119-128 265 260 54 75 2 x M10 1 x M12 1122
1
No results