LDSTR-HT Cable Cleat

ETIM Classification

EC004588

High temperature, light duty single/trefoil formation cable cleat with aluminium base and 2 loop stainless steel strap

Description

The CMP Cyclone I High Temperature is a single/parallel/trefoil composite cable cleat, designed and tested in accordance with IEC 61914. Manufactured from 5000 Series Aluminium, 316L Stainless Steel Strap with high temperature resistant Low Smoke & Fume (LSF) polymeric liners to protect the cable sheath and enable the cable cleat to withstand temperatures of -50°C to +90°C during normal operation. The cable cleat design caters for a wide range of miscellaneous cable shapes and formations. The Cyclone product has an exceptional overlapping cable acceptance range and provides the end user more flexibility in comparison to more rigid cable cleats on the market. Each cleat is capable of securing various cable formations, such as single cable (multicore), single cable in parallel formation or three cables in trefoil formation. The three M10 fixing clearance holes in the base allows versatility of fixing the cleat to the mounting structure.


Features

  • Third party certified to IEC 61914, GOST-R
  • 5000 Series Aluminium, 316L Stainless Steel Strap
  • Single/Parallel/Trefoil formation
  • Short circuit rating of 124kA
  • Operating temperature -50°C to +90°C
  • Combined single (M10) or two bolt (M10) base fixing

Additional Information

Certification
Technical Specification
Axial Load Test Range, IEC 61914 clause 9.4 300N
Cable Formation Trefoil
Classification IEC61914 clause 6.1 6.1.3 Composite
Cleat Material 5000 Series Aluminium, 316L Stainless Steel Strap with high temperature V0 flame retardant polymer liners
Conductor centres - A (mm) 36
Conductor centres - B (mm) 38
Conductor centres - C (mm) 36
Conductor centres - D (mm) 38
Fixed cleat centres A (mm) 300
Fixed cleat centres B (mm) 300
Fixed cleat centres C (mm) 300
Fixed cleat centres D (mm) 300
Impact Resistance, IEC 61914 clause 6.3 Very heavy
kA RMS - A 56.3
kA RMS - B 29
kA RMS - C 52.7
kA RMS - D 29
Lateral Load Test Range, IEC 61914 clause 9.3 3kN
Needle Flame Test, IEC61914 clause 10, 10.1, IEC 60695-11-5 Pass 120 Second
No of tests - A 1
No of tests - B 1
No of tests - C 2
No of tests - D 2
Peak short circuit current A (kA) 124
Peak short circuit current B (kA) 61
Peak short circuit current C (kA) 116
Peak short circuit current D (kA) 61
SC Duration A (Seconds) 0.1
SC Duration B (Seconds) 3
SC Duration C (Seconds) 0.1
SC Duration D (Seconds) 3
Temperature For Permanent Application, IEC 61914 clause 6.2 -50°C to +90°C