QHDSS Cable Cleat

ETIM Classification

EC004588

Top opening heavy duty stainless steel, hinged quad cable cleat

Description

The CMP Mercury is a quad composite cable cleat, designed and tested in accordance with IEC 61914. Manufactured from 316L Stainless Steel with Low Smoke & Fume, Zero Halogen (LSF0H), Phosphorus free polymeric liners to protect the cable sheath. The cleat is designed to accept four cables of the same size, for example three phase power cables plus a neutral cable. The cable cleat has been designed and tested for high short circuit fault withstand on cables held in quad formation, to ensure the securing and retention of cables without cable damage. The two M10 and one M12 fixing clearance holes in the base allows versatility of fixing the cleat to the mounting structure.


Features

  • Third party certified to IEC 61914
  • 316L Stainless Steel
  • Quad formation
  • Short circuit rating of 189kA
  • Operating temperature -60°C to +60°C
  • Combined single (M12) or two bolt (M10) base fixing

Additional Information

Certification
Technical Specification
Axial Load Test Range, IEC 61914 clause 9.4 800-1000N
Cable Formation Quad
Classification IEC61914 clause 6.1 6.1.3 Composite
Cleat Material 316L Stainless Steel with standard liners. Liners are classified as Low Smoke & Fume (LSF), Zero Halogen (LS0H) and Phosphorus Free.
Conductor centres - A (mm) 38
Conductor centres - B (mm) 38
Conductor centres - C (mm) 38
Conductor centres - D (mm) 38
Fixed cleat centres A (mm) 300
Fixed cleat centres B (mm) 300
Fixed cleat centres C (mm) 600
Fixed cleat centres D (mm) 600
Impact Resistance, IEC 61914 clause 6.3 Very heavy
kA RMS - A 85.9
kA RMS - B 46.6
kA RMS - C 63.1
kA RMS - D 63.1
Lateral Load Test Range, IEC 61914 clause 9.3 2-4kN
Needle Flame Test, IEC61914 clause 10, 10.1, IEC 60695-11-5 Pass 120 Second
No of tests - A 1
No of tests - B 1
No of tests - C 1
No of tests - D 1
Peak short circuit current A (kA) 189
Peak short circuit current B (kA) 98
Peak short circuit current C (kA) 139
Peak short circuit current D (kA) 139
SC Duration A (Seconds) 0.1
SC Duration B (Seconds) 1
SC Duration C (Seconds) 0.1
SC Duration D (Seconds) 0.1
Temperature For Permanent Application, IEC 61914 clause 6.2 -60°C to +60°C

Downloads

Certificates

Product Selector

1
Part Number Cable Ø range take (mm) Width (W) Height (H) Depth (D) Hole Pitch (P) Base Fixing Ø (D1) Base Fixing Ø (D2) Weight (g)
QHDSS016020 16-20 66 89 58 1 x M10 430
QHDSS019023 19-23 69 95 58 1 x M10 440
QHDSS021027 21-27 76 103 58 1 x M10 513
QHDSS026031 26-31 80 111 58 1 x M10 516
QHDSS030034 30-34 83 117 58 1 x M10 524
QHDSS031035 31-35 84 119 55 1 x M10 535
QHDSS033037 33-37 87 122 55 25 2 x M10 1 x M12 537
QHDSS036040 36-40 93 129 55 25 2 x M10 1 x M12 546
QHDSS039043 39-43 99 135 55 25 2 x M10 1 x M12 553
QHDSS041045 41-45 103 139 55 25 2 x M10 1 x M12 575
QHDSS044047 44-47 107 142 55 25 2 x M10 1 x M12 562
QHDSS046051 46-51 113 149 55 50 2 x M10 1 x M12 643
QHDSS049053 49-53 119 155 55 50 2 x M10 1 x M12 649
QHDSS052056 52-56 125 161 55 50 2 x M10 1 x M12 664
QHDSS055059 55-59 131 167 55 50 2 x M10 1 x M12 667
QHDSS058062 58-62 137 173 55 50 2 x M10 1 x M12 686
QHDSS061065 61-65 143 179 55 50 2 x M10 1 x M12 703
QHDSS064068 64-68 149 185 55 75 2 x M10 1 x M12 812
QHDSS067071 67-71 155 191 55 75 2 x M10 1 x M12 830
1
No results

0 of 19 Selected