The CMP Conqueror is a trefoil composite cable cleat, designed and tested in accordance with IEC 61914. Manufactured from 316L Stainless Steel with Low Smoke & Fume, Zero Halogen (LSF0H), Phosphorus free polymeric liners to protect the cable sheath. The cable cleat offers a large cable diameter acceptance range due its unique hinge design, which reduces the number of different size cleats required for an installation. The cable cleat has been designed and tested for high short circuit fault withstand on cables held in trefoil formation, to ensure the securing and retention of cables without cable damage. The two M10 and one M12 fixing clearance holes in the base allows versatility of fixing the cleat to the mounting structure.


Features

  • Third party certified to IEC 61914, DNV, Lloyds, Bureau Veritas, ABS, UL, GOST-R, LUL
  • 316L Stainless Steel
  • Trefoil formation
  • Short circuit rating of 170kA
  • Operating temperature -60°C to +60°C
  • Combined single (M12) or two bolt (M10) base fixing

Additional Information

Certification
Technical Specification
Axial Load Test Range, IEC 61914 clause 9.4 800N-1100N
Cable Formation Trefoil
Classification IEC61914 clause 6.1 6.1.3 Composite
Cleat Material 316L Stainless Steel with standard liners. Liners are classified as Low Smoke & Fume (LSF), Zero Halogen (LS0H) and Phosphorus Free.
Conductor centres - A (mm) 36
Conductor centres - B (mm) 36
Conductor centres - C (mm) 36
Conductor centres - D (mm) 36
Fixed cleat centres A (mm) 300
Fixed cleat centres B (mm) 300
Fixed cleat centres C (mm) 600
Fixed cleat centres D (mm) 600
Impact Resistance, IEC 61914 clause 6.3 Very heavy
kA RMS - A 77.3
kA RMS - B 43.2
kA RMS - C 59.6
kA RMS - D 38.1
Lateral Load Test Range, IEC 61914 clause 9.3 4kN-9kN
Needle Flame Test, IEC61914 clause 10, 10.1, IEC 60695-11-5 Pass 120 Second
No of tests - A 1
No of tests - B 1
No of tests - C 2
No of tests - D 2
Peak short circuit current A (kA) 170
Peak short circuit current B (kA) 90
Peak short circuit current C (kA) 131
Peak short circuit current D (kA) 80
SC Duration A (Seconds) 0.1
SC Duration B (Seconds) 1
SC Duration C (Seconds) 0.1
SC Duration D (Seconds) 1
Temperature For Permanent Application, IEC 61914 clause 6.2 -60°C to +60°C

Downloads

Certificates

Product Selector

1
Part Number Cable Ø range take (mm) Width (W) Height (H) Depth (D) Hole Pitch (P) Base Fixing Ø (D1) Base Fixing Ø (D2) Weight (g)
RTSS023032 23-32 122 99 54 25 2 x M10 1 x M12 509
RTSS030039 30-39 126 111 54 25 2 x M10 1 x M12 534
RTSS037046 37-46 132 117 54 25 2 x M10 1 x M12 557
RTSS044053 44-53 151 128 54 50 2 x M10 1 x M12 676
RTSS051060 51-60 154 139 54 50 2 x M10 1 x M12 694
RTSS058067 58-67 157 151 54 50 2 x M10 1 x M12 727
RTSS065074 65-74 176 163 54 75 2 x M10 1 x M12 839
RTSS072081 72-81 182 175 54 75 2 x M10 1 x M12 866
RTSS079088 79-88 191 190 54 75 2 x M10 1 x M12 900
RTSS086095 86-95 216 202 54 75 2 x M10 1 x M12 1023
RTSS093102 93-102 222 215 54 75 2 x M10 1 x M12 1050
RTSS100109 100-109 228 228 54 75 2 x M10 1 x M12 1079
RTSS107116 107-116 254 241 54 75 2 x M10 1 x M12 1199
RTSS114123 114-123 257 254 54 75 2 x M10 1 x M12 1228
RTSS121130 121-130 268 267 54 75 2 x M10 1 x M12 1255
1