SDSTR Cable Cleat

ETIM Classification

EC004588

Standard duty single/trefoil formation cable cleat with stainless steel base and 2 loop stainless steel strap

Description

The CMP Cyclone II is a single/parallel/trefoil composite cable cleat, designed and tested in accordance with IEC 61914. Manufactured from 316L Stainless Steel base and Strap with Low Smoke & Fume, Zero Halogen (LSF0H), Phosphorus free polymeric liners to protect the cable sheath. The cable cleat design caters for a wide range of miscellaneous cable shapes and formations. The Cyclone product has an exceptional overlapping cable acceptance range and provides the end user more flexibility in comparison to more rigid cable cleats on the market. Each cleat is capable of securing various cable formations, such as single cable (multicore), single cable in parallel formation or three cables in trefoil formation. The two M10 and one M12 fixing clearance holes in the base allows versatility of fixing the cleat to the mounting structure.


Features

  • Third party certified to IEC 61914, DNV, Lloyds, Bureau Veritas, ABS, UL, GOST-R, LUL
  • 316L Stainless Steel base and Strap
  • Single/Parallel/Trefoil formation
  • Short circuit rating of 151kA
  • Operating temperature -50°C to +40°C
  • Combined single (M12) or two bolt (M10) base fixing

Additional Information

Certification
Technical Specification
Axial Load Test Range, IEC 61914 clause 9.4 400N
Cable Formation Trefoil
Classification IEC61914 clause 6.1 6.1.3 Composite
Cleat Material 316L Stainless Steel base and Strap.Standard liners are classified as Low Smoke & Fume (LSF), Zero Halogen (LS0H) and Phosphorus Free
Conductor centres - A (mm) 36
Conductor centres - B (mm) 36
Conductor centres - C (mm) 36
Conductor centres - D (mm) 36
Fixed cleat centres A (mm) 300
Fixed cleat centres B (mm) 300
Fixed cleat centres C (mm) 600
Fixed cleat centres D (mm) 600
Impact Resistance, IEC 61914 clause 6.3 Very heavy
kA RMS - A 68.6
kA RMS - B 35.6
kA RMS - C 54.5
kA RMS - D 32.8
Lateral Load Test Range, IEC 61914 clause 9.3 5.5-20kN
Needle Flame Test, IEC61914 clause 10, 10.1, IEC 60695-11-5 Pass 120 Second
No of tests - A 1
No of tests - B 1
No of tests - C 2
No of tests - D 2
Peak short circuit current A (kA) 151
Peak short circuit current B (kA) 80
Peak short circuit current C (kA) 120
Peak short circuit current D (kA) 70
SC Duration A (Seconds) 0.1
SC Duration B (Seconds) 1
SC Duration C (Seconds) 0.1
SC Duration D (Seconds) 1
Temperature For Permanent Application, IEC 61914 clause 6.2 -50°C to +40°C

Downloads

Certificates

Product Selector

1
Part Number Cable Ø range take (mm) Width (W) Height (H) Depth (D) Hole Pitch (P) Base Fixing Ø (D1) Base Fixing Ø (D2) Weight (g)
2CYC024034 24-34 108 96 89 80 2 x M10 1 x M12 441
2CYC030041 30-41 108 109 89 80 2 x M10 1 x M12 454
2CYC037047 37-47 128 120 89 100 2 x M10 1 x M12 518
2CYC043054 43-54 128 134 89 100 2 x M10 1 x M12 527
2CYC050060 50-60 148 145 89 120 2 x M10 1 x M12 611
2CYC056067 56-67 148 158 89 120 2 x M10 1 x M12 623
2CYC063073 63-73 168 170 89 140 2 x M10 1 x M12 685
2CYC069080 69-80 168 183 89 140 2 x M10 1 x M12 696
2CYC072085 72-85 188 193 89 160 2 x M10 1 x M12 795
2CYC082095 82-95 188 212 89 160 2 x M10 1 x M12 812
2CYC092105 92-105 210 231 89 100 2 x M10 1 x M12 868
2CYC102115 102-115 210 250 89 100 2 x M10 1 x M12 886
2CYC112125 112-125 235 269 89 100 2 x M10 1 x M12 999
2CYC122135 122-135 235 288 89 100 2 x M10 1 x M12 1018
2CYC132145 132-145 250 307 89 120 2 x M10 1 x M12 1077
1
No results

0 of 15 Selected