SSDSS Cable Cleat

ETIM Classification

EC004588

Top opening standard duty stainless steel, single formation cable cleat

Description

The CMP Emerald is a single composite cable cleat, designed and tested in accordance with IEC 61914. Manufactured from 316L Stainless Steel with Low Smoke & Fume, Zero Halogen (LSF0H), Phosphorus free polymeric liners to protect the cable sheath. The top opening is designed to fit more cleats installed side-by-side. Flexible materials allow a wide opening for easy cable installation and the cleat is easily formed around the cables for closure. The three M10 fixing clearance holes in the base allows versatility of fixing the cleat to the mounting structure.


Features

  • Third party certified to IEC 61914, GOST-R
  • 316L Stainless Steel
  • Single formation
  • Short circuit rating of 155kA
  • Operating temperature -60°C to +60°C
  • Combined single (M10) or two bolt (M10) base fixing

Additional Information

Certification
Technical Specification
Axial Load Test Range, IEC 61914 clause 9.4 Information on request
Cable Formation Single
Classification IEC61914 clause 6.1 6.1.3 Composite
Cleat Material 316L Stainless Steel with standard liners. Liners are classified as Low Smoke & Fume (LSF), Zero Halogen (LS0H) and Phosphorus Free.
Conductor centres - A (mm) 105
Conductor centres - B (mm) 105
Conductor centres - C (mm) 105
Conductor centres - D (mm) 105
Fixed cleat centres A (mm) 600
Fixed cleat centres B (mm) 600
Fixed cleat centres C (mm) 600
Fixed cleat centres D (mm) 600
Impact Resistance, IEC 61914 clause 6.3 Very heavy
kA RMS - A 73.8
kA RMS - B 38.5
kA RMS - C 73.5
kA RMS - D 38.5
Lateral Load Test Range, IEC 61914 clause 9.3 Information on request
Needle Flame Test, IEC61914 clause 10, 10.1, IEC 60695-11-5 Pass 120 Second
No of tests - A 1
No of tests - B 1
No of tests - C 2
No of tests - D 2
Peak short circuit current A (kA) 155
Peak short circuit current B (kA) 80.8
Peak short circuit current C (kA) 154
Peak short circuit current D (kA) 80.8
SC Duration A (Seconds) 0.1
SC Duration B (Seconds) 1
SC Duration C (Seconds) 0.1
SC Duration D (Seconds) 1
Temperature For Permanent Application, IEC 61914 clause 6.2 -60°C to +60°C

Downloads

Certificates

Product Selector

1
Part Number Cable Ø range take (mm) Width (W) Height (H) Depth (D) Hole Pitch (P) Base Fixing Ø (D1) Base Fixing Ø (D2) Weight (g)
SSDSS019026 19-26 54 66 58 1 xM10 243
SSDSS025032 25-32 55 72 58 1 xM10 252
SSDSS030042 30-42 58 82 58 1 xM10 266
SSDSS040050 40-50 60 91 58 1 xM10 278
SSDSS048058 48-58 71 99 53 25 2 x M10 1 xM10 283
SSDSS056066 56-66 76 107 53 25 2 x M10 1 xM10 295
SSDSS064074 64-74 84 115 53 25 2 x M10 1 xM10 305
SSDSS072082 72-82 92 123 53 25 2 x M10 1 xM10 320
SSDSS080090 80-90 100 131 53 25 2 x M10 1 xM10 333
SSDSS088098 88-98 108 139 53 50 2 x M10 1 xM10 394
SSDSS096106 96-106 116 147 53 50 2 x M10 1 xM10 406
SSDSS105115 105-115 125 156 53 50 2 x M10 1 xM10 420
1
No results